Recently viewed items
Schneider multifunction control relay RM17-TE - range 183..528 V AC RM17TE00
This Harmony RM17-TE relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase supply control [...]
Model :RM17TE00
SKU :
This item cannot be returned or exchanged
Cash on Delivery available
- Condition: New
Description for Schneider multifunction control relay RM17-TE - range 183..528 V AC RM17TE00
This Harmony RM17-TE relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase supply control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. The product monitors its own power supply, when the power supply is abnormal, the output relay de-energizes. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
Specifications
Range of product | Harmony Control Relays |
---|---|
product or component type | 3-phase control relay |
Relay type | Multifunction control relay |
Product specific application | For 3-phase supply |
Relay name | RM17TE |
Relay monitored parameters | Undervoltage and overvoltage in window mode Asymmetry Phase sequence Phase failure detection |
time delay | Adjustable 0.1...10 s, +/- 10 % of the full scale value |
Switching capacity in VA | 1250 VA |
Measurement range | 208...480 V voltage AC |
Contacts type and composition | 1 C/O |
[Uc] control circuit voltage | 208...480 V |
Reset time | 1500 ms time delay |
---|---|
Maximum switching voltage | 250 V AC 250 V DC |
Minimum switching current | 10 mA at 5 V DC |
Maximum switching current | 5 A AC 5 A DC |
Supply voltage limits | 183…528 V AC |
Control circuit voltage limits | - 12 % + 10 % Un |
Power consumption in VA | 0…22 VA at 400 V AC 50 Hz |
control circuit frequency | 50...60 Hz +/- 10 % |
Output contacts | 1 C/O |
Nominal output current | 5 A |
Measurement voltage limits | 183…528 V AC |
Hysteresis | 2 % |
delay at power up | 650 ms |
Maximum measuring cycle | 150 ms measurement cycle as true rms value |
Threshold adjustment voltage | -2...-17 % in the range 220 V AC +2...+10 % in the range 480 V AC -2...-12 % in the range 208 V AC 2...20 % of Un selected |
Voltage range | 208...480 V phase to phase |
Adjustment of asymmetry threshold | 5...15 % of Un selected |
Repeat accuracy | 0.5 % for input and measurement circuit 3 % for time delay |
Measurement error | < 0.05 %/°C with temperature variation < 1 % over the whole range with voltage variation |
Phase failure sensitivity | 0.7 Un |
Response time | < 200 ms (in the event of a fault) |
Marking | CE |
Overvoltage category | III conforming to IEC 60664-1 |
Insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1 |
[Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
Supply frequency | 50/60 Hz +/- 10 % |
Operating position | Any position without derating |
Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
Housing material | Self-extinguishing plastic |
Local signalling | LED (green) for power ON LED (yellow) for relay ON |
Mounting support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
Electrical durability | 100000 cycles |
Mechanical durability | 30000000 cycles |
Operating rate | <= 360 operations/hour full load |
Utilisation category | AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
Safety reliability data | MTTFd = 502.2 years B10d = 470000 |
width | 17.5 mm |
net weight | 0.13 kg |
Electromagnetic compatibility | Emission standard for industrial environments conforming to EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Immunity for industrial environments conforming to EN/IEC 61000-6-2 |
---|---|
Standards | EN/IEC 60255-1 |
Product certifications | GOST C-Tick CSA UL GL |
Directives | 89/336/EEC - electromagnetic compatibility 73/23/EEC - low voltage directive |
Ambient air temperature for storage | -40…70 °C |
Ambient air temperature for operation | -20…50 °C |
Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
Vibration resistance | 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1 |
Shock resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
IP degree of protection | IP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529 |
Pollution degree | 3 conforming to IEC 60664-1 |
Dielectric test voltage | 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1 |
Non-dissipating shock wave | 4 kV conforming to IEC 60255-5 4 kV conforming to IEC 60664-1 4 kV conforming to IEC 61000-4-5 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 2.7 cm |
Package 1 Width | 7.7 cm |
Package 1 Length | 9.6 cm |
Package 1 Weight | 92.0 g |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 48 |
Package 2 Height | 15.0 cm |
Package 2 Width | 30.0 cm |
Package 2 Length | 40.0 cm |
Package 2 Weight | 4.936 kg |
Warranty | 18 months |
---|