Recently viewed items
Schneider Motor circuit breaker, TeSys GV3, 3P, 50 A, magnetic, rotary handle, EverLink terminals GV3L50
Model :GV3L50
SKU :GV3L50
This item cannot be returned or exchanged
Cash on Delivery available
- Condition: New
Description for Schneider Motor circuit breaker, TeSys GV3, 3P, 50 A, magnetic, rotary handle, EverLink terminals GV3L50
TeSys GV motor circuit breaker, 3 poles (3P), 50A/690V, for 3-phase motor applications 22kW@400V. It provides a magnetic protection with a tripping level at 14xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary handle guaranteed for 50 000 cycles AC-3. To complete motor protection, use it in association with a thermal overload relay LRD350 (to be ordered separately). Multi standards certified (IEC, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Features
Main Range TeSys Deca Product name TeSys GV3
TeSys Deca Product or component type Motor circuit breaker Device short name GV3L Device application Motor protection Trip unit technology Magnetic
Complementary Poles description 3P Network type AC Utilisation category Category A conforming to IEC 60947-2 Network frequency 50/60 Hz Fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws) Motor power kW 22 kW at 400/415 V AC 50/60 Hz
30 kW at 500 V AC 50/60 Hz
45 kW at 690 V AC 50/60 Hz Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz
50 kA Icu at 400/415 V AC 50/60 Hz
50 kA Icu at 440 V AC 50/60 Hz
12 kA Icu at 500 V AC 50/60 Hz
6 kA Icu at 690 V AC 50/60 Hz [Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz
100 % at 400/415 V AC 50/60 Hz
100 % at 440 V AC 50/60 Hz
50 % at 500 V AC 50/60 Hz
50 % at 690 V AC 50/60 Hz control type Rotary handle [In] rated current 50 A Magnetic tripping current 700 A [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 Suitability for isolation Yes conforming to IEC 60947-1 Power dissipation per pole 8 W Mechanical durability 50000 cycles Electrical durability 50000 cycles for AC-3 at 415 V In Tightening torque 5 N.m - on screw clamp terminal Width 55 mm height 132 mm Depth 136 mm Net weight 0.96 kg Colour Dark grey
Environment Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1 product certifications CCC
UL
CSA
EAC
LROS (Lloyds register of shipping)
BV
ABS
DNV-GL
UKCA IP degree of protection IP20 conforming to IEC 60529 Climatic withstand Conforming to IACS E10 Ambient air temperature for storage -40…80 °C Fire resistance 960 °C conforming to IEC 60695-2-11 Ambient air temperature for operation -20…60 °C Mechanical robustness Shocks: 15 Gn for 11 ms contactor open
Shocks: 30 Gn for 11 ms contactor closed
Vibrations: 4 Gn, 5...300 Hz Operating altitude 3000 m
Range | TeSys Deca |
---|---|
Product name | TeSys GV3 TeSys Deca |
Product or component type | Motor circuit breaker |
Device short name | GV3L |
Device application | Motor protection |
Trip unit technology | Magnetic |
Poles description | 3P |
---|---|
Network type | AC |
Utilisation category | Category A conforming to IEC 60947-2 |
Network frequency | 50/60 Hz |
Fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) |
Motor power kW | 22 kW at 400/415 V AC 50/60 Hz 30 kW at 500 V AC 50/60 Hz 45 kW at 690 V AC 50/60 Hz |
Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz 50 kA Icu at 400/415 V AC 50/60 Hz 50 kA Icu at 440 V AC 50/60 Hz 12 kA Icu at 500 V AC 50/60 Hz 6 kA Icu at 690 V AC 50/60 Hz |
[Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz 100 % at 400/415 V AC 50/60 Hz 100 % at 440 V AC 50/60 Hz 50 % at 500 V AC 50/60 Hz 50 % at 690 V AC 50/60 Hz |
control type | Rotary handle |
[In] rated current | 50 A |
Magnetic tripping current | 700 A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-1 |
Power dissipation per pole | 8 W |
Mechanical durability | 50000 cycles |
Electrical durability | 50000 cycles for AC-3 at 415 V In |
Tightening torque | 5 N.m - on screw clamp terminal |
Width | 55 mm |
height | 132 mm |
Depth | 136 mm |
Net weight | 0.96 kg |
Colour | Dark grey |
Standards | EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 |
---|---|
product certifications | CCC UL CSA EAC LROS (Lloyds register of shipping) BV ABS DNV-GL UKCA |
IP degree of protection | IP20 conforming to IEC 60529 |
Climatic withstand | Conforming to IACS E10 |
Ambient air temperature for storage | -40…80 °C |
Fire resistance | 960 °C conforming to IEC 60695-2-11 |
Ambient air temperature for operation | -20…60 °C |
Mechanical robustness | Shocks: 15 Gn for 11 ms contactor open Shocks: 30 Gn for 11 ms contactor closed Vibrations: 4 Gn, 5...300 Hz |
Operating altitude | 3000 m |