Recently viewed items
Schneider Electric Harmony Miniature plug-in relay 10A 3 CO with lockable test button 24V AC RXM3AB1B7
Harmony Miniature plug-in relay 10A 3 CO with lockable test button 24V AC
Model :RXM3AB1B7
SKU :RXM3AB1B7
7 days retun policy available
Cash on Delivery available
- Condition: New
Description for Schneider Electric Harmony Miniature plug-in relay 10A 3 CO with lockable test button 24V AC RXM3AB1B7
Schneider Electric Harmony Miniature plug-in relay 10A 3 CO with lockable test button 24V AC RXM3AB1B7
"This Harmony RXM miniature plug-in relay has a coil control voltage of 24V AC and has 3 changeover contacts 3PDT (triple pole double throw) with a rating of 10A." "It has large choice of number of contacts for high rated current use with space-saving design." "It also offers one-step lockable test button and mechanical indicator for contact status." "It helps to reduce the size of enclosures and increase machine reliability, you can mount nearly everywhere." "The product is IP40 and has a transparent cover allowing operator to visually inspect the status of contacts." "Workability for hard-wired logic automated systems to complement the functions of industrial programmable logic controllers (PLCs)." 0 0 0 "It is a green premium product and conforms to international standard and certifications like IEC, CE, UL, CSA, EAC, Lloyd's, RoHS and REACH." "RXM Relay should be used with a RXZE socket (screw clamp, screw connector, push-in terminal). To protect against vibrations, plastic/metal clamp can be added to the socket. Protection modules and marking legend are also available." "It is sold in lots of 10 and reference includes relay only." 0 "The RXM plug-in relays are a series of industrial plug-in relays designed for both simple and complex automation systems and available with 2 CO (12A), 3 CO (10A), 4 CO (6A) contacts, 4 CO (3A) low level contacts." 0 0
Specifications
Range of product | Harmony Electromechanical Relays |
---|---|
Series name | Miniature |
Product or component type | Plug-in relay |
Device short name | RXM |
Contacts type and composition | 3 C/O |
[Uc] control circuit voltage | 24 V AC 50/60 Hz |
Status LED | Without |
Control type | Lockable test button |
utilisation coefficient | 20 % |
Shape of pin | Flat |
---|---|
[Ui] rated insulation voltage | 250 V conforming to IEC 300 V conforming to CSA 300 V conforming to UL |
[Uimp] rated impulse withstand voltage | 4 kV during 1.2/50 µs |
Contacts material | AgNi |
[Ie] rated operational current | 10 A at 28 V (DC) NO conforming to IEC 10 A at 250 V (AC) NO conforming to IEC 5 A at 28 V (DC) NC conforming to IEC 5 A at 250 V (AC) NC conforming to IEC 10 A at 30 V (DC) conforming to UL 10 A at 277 V (AC) conforming to UL |
Continuous output current | 6.7 A |
Maximum switching voltage | 250 V conforming to IEC |
resistive rated load | 10 A at 250 V AC 10 A at 28 V DC |
Maximum switching capacity | 2500 VA/280 W |
Minimum switching capacity | 170 mW at 10 mA, 17 V |
Operating rate | <= 1200 cycles/hour under load <= 18000 cycles/hour no-load |
Mechanical durability | 10000000 cycles |
Electrical durability | 100000 cycles for resistive load |
average coil consumption in VA | 1.2 at 60 Hz |
Average consumption | 1.2 VA at 60 Hz |
Drop-out voltage threshold | >= 0.15 Uc |
operate time | 20 ms |
release time | 20 ms |
average coil resistance | 180 Ohm at 20 °C +/- 15 % |
Rated operational voltage limits | 19.2...26.4 V AC |
Safety reliability data | B10d = 100000 |
Protection category | RT I |
Test levels | Level A group mounting |
Operating position | Any position |
CAD overall height | 79 mm |
CAD overall depth | 78.45 mm |
Net weight | 0.037 kg |
Device presentation | Complete product |
Dielectric strength | 1300 V AC between contacts with micro disconnection 2000 V AC between coil and contact 2000 V AC between poles |
---|---|
Product certifications | GOST CSA Lloyd's CE UL |
Standards | EN/IEC 61810-1 UL 508 CSA C22.2 No 14 |
Ambient air temperature for storage | -40…85 °C |
Ambient air temperature for operation | -40…55 °C |
Vibration resistance | 3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation 5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating |
IP degree of protection | IP40 conforming to EN/IEC 60529 |
Shock resistance | 10 gn for in operation 30 gn for not operating |
Pollution degree | 2 |