Description for Schneider Electric Easy9 Residual Current Circuit Breaker 4P 40A 100 mA AC type 400V EZ9R56440
Schneider Electric Easy9 Residual Current Circuit Breaker 4P 40A 100 mA AC type 400V EZ9R56440
This product is a Easy9 residual current circuit breaker (RCCB). It is a 4P circuit breaker with 40A In rated current, a sensitivity of 100mA with a AC type protection class. This product protects against electrical shock by indirect contact and fire hazards. It also has protection against fire hazards due to persistent earth fault current. This product has a positive contact indications with fault tripping indication on the front panel by the position of the handle (0-I engraved). This is dedicated for residential and small commercial buildings market segment. This product is compliant with IEC 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 500A. The (Inc/IΔc) conditional rated short circuit current is 6000A. The mechanical endurance is going up to 5000 cycles and electrical endurance going up to 2000 cycles. The Ue operational voltage is 400VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product color is light grey (RAL7035). The dimensions are (W) 72mm x (H) 82mm x (D) 72mm. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.
Specifications
Main
Range of product
Easy9
Product or component type
Residual current circuit breaker (RCCB)
Device short name
Easy9 RCCB
Poles
4P
Neutral position
Left
[In] rated current
40 A
Network type
AC
earth-leakage sensitivity
100 mA
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type AC
rated breaking and making capacity
500 A
rated conditional short-circuit current
Easy9 MCB: 6000 A 40 A
Complementary
Device location in system
Outgoer
Network frequency
50/60 Hz
[Ue] rated operational voltage
400 V AC 50/60 Hz
Residual current tripping technology
Voltage independent
[Ui] rated insulation voltage
440 V AC
[Uimp] rated impulse withstand voltage
4 kV
Surge current
250 A
Contact position indicator
Yes
Control type
Toggle
Mounting mode
Clip-on
Mounting support
DIN rail
comb busbar and distribution block compatibility
Top: YES
connection pitch
18 mm between phases
9 mm pitches
8
Height
82 mm
Width
72 mm
Depth
72 mm
colour
Grey (RAL 7035)
Mechanical durability
5000 cycles
electrical durability
AC: 2000 cycles 400 V AC 50/60 Hz
connections - terminals
Tunnel type terminal (top or bottom) 1…35 mm² rigid Tunnel type terminal (top or bottom) 1…25 mm² flexible