Description for Schneider Electric Easy9 Residual Current Circuit Breaker 2P 40A 30mA AC type 230V EZ9R36240
Schneider Electric Easy9 Residual Current Circuit Breaker 2P 40A 30mA AC type 230V EZ9R36240
This Easy9 product is a residual current circuit breaker (RCCB). It is a 2P circuit breaker with 40A In rated current, 30mA earth leakage sensitivity and AC type protection class. This product protects against electrical shock by direct or indirect contact and fire hazards. It also has protection against fire hazards due to persistent earth fault current. This product has a positive contact indications with fault tripping indication on the front panel by the position of the handle (0-I engraved). This is dedicated for residential and small commercial buildings market segment. This product is compliant with IEC 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 500A. The (Inc/IΔc) conditional rated short circuit current is 6000A. It has an electrical endurance going up to 2000 cycles and a mechanical endurance going up to 5000 cycles. The Ue operational voltage is 230VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product color is light grey (RAL7035). The dimensions are (W) 36mm x (H) 82mm x (D) 72mm. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -5°C to 60°C. The storage temperature is from -40°C to 85°C.
Specifications
Main
range of product
Easy9
product or component type
Residual current circuit breaker (RCCB)
device short name
Easy9 RCCB
Poles
2P
neutral position
Left
[In] rated current
40 A
network type
AC
earth-leakage sensitivity
30 mA
earth-leakage protection time delay
Instantaneous
earth-leakage protection class
Type AC
rated breaking and making capacity
500 A
rated conditional short-circuit current
Easy9 MCB: 6000 A 40 A
Complementary
device location in system
Outgoer
network frequency
50/60 Hz
[Ue] rated operational voltage
230 V AC 50/60 Hz
residual current tripping technology
Voltage independent
[Ui] rated insulation voltage
440 V AC
[Uimp] rated impulse withstand voltage
4 kV
surge current
250 A
contact position indicator
Yes
control type
Toggle
mounting mode
Clip-on
mounting support
DIN rail
comb busbar and distribution block compatibility
Top: YES
connection pitch
18 mm between phases
9 mm pitches
4
Height
82 mm
width
36 mm
Depth
72 mm
colour
Grey (RAL 7035)
mechanical durability
5000 cycles
electrical durability
AC: 2000 cycles 230 V AC 50/60 Hz
connections - terminals
Tunnel type terminal (top or bottom) 1…35 mm² rigid Tunnel type terminal (top or bottom) 1…25 mm² flexible