The Schneider ComPacT NSX100B Circuit Breaker is a high-performance protection device designed for robust electrical systems. With a breaking capacity of 25kA at 415VAC, this circuit breaker provides reliable safety and operational efficiency. It features a TMD (Thermal-Magnetic) trip unit with a 100A rating, offering both thermal overload and magnetic short-circuit protection. Engineered to function effectively at temperatures up to 50°C, this breaker is ideal for demanding environments. The 3 poles 3D configuration is well-suited for a variety of commercial and industrial applications.
Specifications
ComPacT NSX New Generation Circuit Breaker Specifications
Main | |
---|---|
Range | ComPacT new generation |
Product name | ComPacT NSX new generation |
Device short name | NSX100B |
Product or component type | Circuit breaker |
Device application | Distribution |
Poles description | 3P |
Protected poles description | 3D |
[In] rated current | 100 A at 50 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
Network type | AC |
Network frequency | 50/60 Hz |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level | B 25 kA 415 V AC |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit protection functions | LI |
Control type | Toggle |
Circuit breaker mounting mode | Fixed |
Complementary | |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ics] rated service short-circuit breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability | 50000 cycles |
Electrical durability | 50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In |
Power dissipation per pole | 8.8 W |
Mounting support | Backplate |
Mounting position | Horizontal and vertical Flat on the back |
Upside connection | Front |
Downside connection | Front |
Connection pitch | 35 mm |
Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
Trip unit rating | 100 A at 50 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
[Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
Long-time protection delay adjustment type tr | Fixed |
[tr] long-time protection delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir |
Instantaneous protection pick-up adjustment type Ii | Fixed |
[Ii] instantaneous protection pick-up adjustment range | 800 A |
Earth-leakage protection | Without |
Number of slots for electrical auxiliaries | 5 slot(s) |
Width (W) | 105 mm |
Height (H) | 161 mm |
Depth (D) | 86 mm |
Net weight | 2.05 kg |
Environment | |
Standards | EN/IEC 60947-2 |
Overvoltage category | Class II |
Electrical shock protection class | Class II |
Pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -50…85 °C |
Relative humidity | 0…95 % |
Operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |
Packing Units | |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |