Free UAE Shipping on orders over 100 AED
+971 52 2525774   |   [email protected] Cash on Delivery   |   Express Delivery | Free Returns | Our Location
Recently viewed items

Fluke 393 FC Solar Clamp Meter CAT III 1500 V

Fluke 393 FC Solar Clamp Meter CAT III 1500 V
Model :393
SKU :393
Assured

No Return This item cannot be returned or exchanged
Cash on Delivery Cash on Delivery available
AED 3,613.00
Rate inclusive of VAT
Sold By : MEPKart
Fulfilled by Thomsun Industries

100%
- +
Bulk Order

  •  Condition: New

Description for Fluke 393 FC Solar Clamp Meter CAT III 1500 V


Fluke 393 FC Solar Clamp Meter CAT III 1500 V

Key features

  • Measure safely with CAT III 1500 V rated clamp meter
  • Thin jaw for access to cables in crowded combiner boxes
  • Sturdy IP54 rated for outdoor use and solar installation
  • Work efficiently with dc power measurement, audio polarity and visual continuity

Specifications


Specifications: Fluke 393 FC Solar Clamp Meter CAT III 1500 V


Specifications:   
General   
Maximum voltage between any Terminal and Earth Ground  
AC1000 V  
DC1500 V  
Batteries2 AA IEC LR6 alkaline  
DisplayDual display with backlight  
Automatic Power Off20 minutes  
Electrical   
Accuracy   
Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, relative humidity at 0 % to 75 %. Accuracy specifications take the form of: ±([% of Reading] + [Number of Least Significant Digits]).
Temperature CoefficientsAdd 0.1 x specified accuracy for each °C > 28 °C or < 18 °C
AC Current: Jaw   
Range999.9 A  
Resolution0.1 A  
Accuracy2 % + 5 digits (10 Hz to 100 Hz) 
 2.5 % + 5 digits (100 Hz to 500 Hz) 
Crest Factor (50/60 Hz)2.5 @600.0 A  
 3.0 @500.0 A  
 1.42 @999.9 A  
 Add 2 % for C.F. >2  
AC Current: Flexible Current Probe   
Range999.9 A  
 2500 A  
Resolution0.1 A (≤999.9 A)  
 1 A (≤2500 A)  
Accuracy3 % RD + 5 digits (10 Hz to 500 Hz) 
Crest Factor (50/60Hz)2.5 @1400 A  
 3.0 @1100 A  
 1.42@2500 A  
 Add 2 % for C.F. >2  
Position Sensitivity   
NEC symbol
Distance from Optimumi2500-10 Flexi2500-18 FlexError
A0.5 in (12.7 mm)1.4 in (35.6 mm)±0.5 %
B0.8 in (20.3 mm)2.0 in (50.8 mm)±1.0 %
C1.4 in (35.6 mm)2.5 in (63.5 mm)±2.0 %
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range.
    
DC Current   
Range999.9 A  
Resolution0.1 A  
Accuracy2 % RD + 5 digits[1]  
 [1] When using the ZERO (B) function to compensate for offsets.
AC Voltage   
Range600.0 V  
 1000 V  
Resolution0.1 V (≤600.0 V)  
 1 V (≤1000 V)  
Accuracy1 % RD + 5 digits (20 Hz to 500 Hz) 
DC Voltage   
Range600.0 V  
 1500 V  
Resolution0.1 V (≤600.0 V)  
 1 V (≤1500 V)  
Accuracy1 % RD + 5 digits  
mV dc   
Range500.0 mV  
Resolution0.1 mV  
Accuracy1 % RD + 5 digits  
Amps Frequency: Jaw   
Range5.0 Hz to 500.0 Hz  
Resolution0.1 Hz  
Accuracy0.5 % RD + 5 digits  
Trigger Level5 Hz to 10 Hz, ≥10 A  
 10 Hz to 100 Hz, ≥5 A  
 100 Hz to 500 Hz, ≥10 A  
Amps Frequency: Flexible Current Probe   
Range5.0 Hz to 500.0 Hz  
Resolution0.1 Hz  
Accuracy0.5 % RD + 5 digits  
Trigger Level5 Hz to 20 Hz, ≥25 A  
 20 Hz to 100 Hz, ≥20 A  
 100 Hz to 500 Hz, ≥25 A  
Voltage Frequency   
Range5.0 Hz to 500.0 Hz  
Resolution0.1 Hz  
Accuracy0.5 % RD + 5 digits  
Trigger Level5 Hz to 20 Hz, ≥5 V  
 20 Hz to 100 Hz, ≥5 V  
 100 Hz to 500 Hz, ≥10 V  
DC Power   
Range600.0 kVA (600.0 V dc range)  
 1500 kVA (1500 V dc range)  
Resolution0.1 kVA  
 1 kVA  
Accuracy2 % RD + 2.0 kVA 

Customer Reviews


Write a review


Please login or register to review